Natural Gas Generator Canopy Gas Engine Bio Gas Engine Generator Sets Gas Generator
Natural gas can be used by home application, Electricity generation, industrial chemical and industrial fuel and so on.It is a good substitute of coal and petroleum.It can instead of civil coal gas, it can be used as nitrogenous fertilizer instead of coal and petroleum, it can be used as ethylene of naphtha, it also can be used as the car engine fuel instead of petroleum.
Requirements for Natural Gas Gen-set
Within 1m from pressure valve of gas intake
1.Pressure 80~200Kpa, pressure changing rate≤1kpa/min
2.H2S≤200mg/Nm3
3.CH4 content≥70%, changing rate≤2%min
4.Impurity particle size ≤5μm, Impurity particle content ≤30mg/Nm3
5.Moisture content ≤40g/Nm3
Noted:If fuel gas contains higher quantity of sulfur and ammonia, it not only corrodes the pole of sparking plug seriously, but also increases the acid value, which corrodes internal parts of genset and corrodes the genset with precipitates.
Main Specification
Natural gas can be used by home application, Electricity generation, industrial chemical and industrial fuel and so on.It is a good substitute of coal and petroleum.It can instead of civil coal gas, it can be used as nitrogenous fertilizer instead of coal and petroleum, it can be used as ethylene of naphtha, it also can be used as the car engine fuel instead of petroleum.
Requirements for Natural Gas Gen-set
Within 1m from pressure valve of gas intake
1.Pressure 80~200Kpa, pressure changing rate≤1kpa/min
2.H2S≤200mg/Nm3
3.CH4 content≥70%, changing rate≤2%min
4.Impurity particle size ≤5μm, Impurity particle content ≤30mg/Nm3
5.Moisture content ≤40g/Nm3
Noted:If fuel gas contains higher quantity of sulfur and ammonia, it not only corrodes the pole of sparking plug seriously, but also increases the acid value, which corrodes internal parts of genset and corrodes the genset with precipitates.
Main Specification
Genset model | CW-400GFT |
Engine No. | 12V190DT-2 |
Gas mix type | Outside |
Rated power | 400kW |
Continuous power | 320kW |
Rated voltage | 400v/230v |
Phase | 3phase4wire |
Rated frequency | 50Hz |
Rated rotation | 1000r/min |
Rated power factor | 0.8 |
Rated current | 720A |
Frequency volatility rate | ≤0.5% |
Voltage regulating rage | 95-105% |
Heat consumption | ≤11.5mj/kw.H |
Lubricant consumption | ≤1.5g/kw.H |
Gas pressure | 80-200kpa |
Cylinder number | 12 v |
Cylinder diameter | 190mm |
Stroke | 210mm |
Compression ratio | 9:1 |
Starting mode | 24V electric motor |
Overhaul time | ≥25000h |
Noise | ≤85dB |
Intake mode | Natural intake |
Sparking mode | Sparking plug |
Voltage regulation mode | Automatic |
Speed regulation mode | Electric speed regulate |
Lubrication mode | Pressure and splash |
Cooling mode | Circulating water cooled |
Exhaust temperature | ≤650ºC |
Displacement | 71.45L |
Genset size | 6000*1970*2235mm |